6.4 Power fail signal (PF) and power fail 电源故障信号和电源故障 I/O modules maintain the last values until they have recognized the connection interruption and then adopt safety values until the CPU module sends actual values after restart. In case of power failure of the I/O module, output levels adopt zero voltage and/or zero current. I/O模板识别出最后一次值直到它们识别出连接中断,然后采取安全值,直到CPU发送实际值后重新启动。当IO模块断电时,输出零电压和/或零电流。 After voltage returns, I/O modules only change their output level when the CPU module communicates actual values. 恢复电压后,当CPU模板通讯实际值时,I/O模板改变其输出值。 6.4.1Power fail signal (PF) and no power fail 电源故障信号(PF)和断电故障PF < 15 ms 电源故障时间 < 15ms | While the power fail signal is active, the CPU module or the AC 800F controller does not communicate current values; I/O modules independently maintain the last values. 当电源故障信号激活,CPU模块或者AC 800F控制器无法通讯当前值;I/O模块 独立的保持前一次的数值。 |
PF > 15 ms 电源故障时间 > 15ms | I/O modules maintain the last values until they have recognized the connection interruption to the CPU module or to the AC 800F controller before they adopt the configured safety values The safety value are maintained until the AC 800F controller has performed a warm start and provides the I/O modules with new values. 在采取设定的安全值之前,I/O模板保持最近的数值直到识别出与CPU模板或者 AC 800F控制器的连接中断。保持安全值直到AC 800F执行热启动,提供I/O 模板新的数值。 |
A possible power failure can be evaluated by means of a system variable and used in the user program. 可能的电源故障可以通过系统变量来评估,使用在用户程序中。 |