5.1.3 Redundancy criteria
冗余准则
A redundancy toggle between Primary and Secondary is forced when the self-test diagnosis reveals the following conditions:
当自建诊断显示以下情况时,强制在主(控制器)和备(控制器)之间发生冗余切换。
- a module fault has occurred (a module fault is also detected, when a fieldbus module is switched off),
- 模块故障发生(当现场总线模块关闭时,也检测到模块故障)
- an equipment fault has been detected on the fieldbus module
- 现场总线模块上检测到模块故障
- the watchdog has responded due to a controller hardware error
- 看门狗相应控制器硬件错误
- a power fail of the power supply is reported
- 报告电源故障
- a network fault has occurred
- 发生网络故障
- a “fatal software error” has occurred
- 发生致命软件错误
If the redundant link is interrupted, a redundancy toggle is initiated. The previous Primary remains in the “no operating system“ status. When the redundancy link is re-established, a reset must be initiated in the Secondary.
如果冗余链路断开,则启动冗余切换。之前的Primary仍然处于“无操作系统”状态。当冗余链路重新建立时,必须在从备(控制器)启动复位。
If the Ethernet interface for the redundancy link on the Secondary fails, no redundancy toggle is performed. When the Ethernet interface for the redundancy link on the Secondary operates again, a reset must be initiated in the Secondary.
如果冗余链路的以太网接口故障,冗余切换不会执行。当备控制器上的冗余链路以太网接口再次运行时,必须从备控制器复位操作。